Key points of fire safety inspection in crowded places of hotel projects
Key points of fire safety inspection in crowded places of hotel projects

1. Fire safety management inspection of the unit

1. The fire safety organization is sound;

2. The fire safety management system is perfect;

3. Implement daily fire safety management. There are strict management measures for fire hazards, and regular fire prevention inspections and inspections are organized to discover and eliminate fire hazards in a timely manner.

4. Personnel in key positions have been specially trained and certified to work. Employees will call the police, extinguish the initial fire, and organize personnel evacuation;

5. Regularly inspect, inspect and maintain fire-fighting facilities, and have detailed and complete records;

6. Complete fire extinguishing and emergency evacuation plans, and regular drill records;

7. The fire alarm disposal of the unit is timely and accurate. For places equipped with automatic fire alarm systems, randomly select a detector to blow smoke or manually alarm, after the alarm is issued, the on-duty officer or full-time (part-time) firefighter carries a portable fire extinguisher to the scene to confirm, and reports to the fire control room in time. The on-duty officer or full-time (part-time) firefighter will correctly use fire extinguishers, fire hose reels, indoor fire hydrants, etc. to extinguish the initial fire.

2. Fire control room inspection

1. There are no less than 2 attendants on duty, who have been trained and are certified to work;

2. Have daily duty records, complete and accurate records;

3. There are equipment inspection records, and the records are complete and accurate;

4. The attendant can be proficient in the "Fire Control Room Management and Emergency Procedures", and can skillfully operate the fire control equipment;

5. The fire control equipment is in normal operation, can correctly display the fire alarm signal and the action and status signal of the fire protection facilities, and can correctly print the relevant information.

3. Fire separation inspection

1. The fireproof partition and fireproof separation facilities meet the requirements;

2. There is no obstacle under the fire shutter. Automatic and manual start of the fire shutter, the shutter can fall to the floor, and the feedback signal is correct;

3. Pipe wells, cable wells, and holes where pipelines and cables pass through the floor and wall are sealed and compacted;

4. Kitchens, power distribution rooms, boiler rooms, diesel generator rooms and other parts with greater fire risk are separated from other surrounding places by strict fire separation, and there are strict fire prevention measures and strict fire safety management systems.

Fourth, personnel safety evacuation system inspection

1. The number, type and installation height of evacuation indication signs and emergency lighting meet the requirements, and the evacuation indication signs can be clearly seen on the evacuation route and clearly point to the safety exit;

2. The main and standby power switching functions of the emergency lighting are normal, and the emergency lighting can shine normally after the main power is cut off;

3. The fire emergency broadcast can be broadcast in different areas to correctly guide the evacuation of personnel;

4. The fire door of the closed staircase, smoke-proof staircase and its front room is opened in the direction of evacuation, with self-closing function, and is in a normally closed state; the fire door that needs to be normally opened due to frequent use can be automatically and manually closed; the evacuation door that needs to control personnel to enter and exit at will can be opened from the inside without any tools, and there are obvious signs and use tips; the opening and closing state of the normally open fire door can be correctly displayed in the fire control room;

5. The safety exits, evacuation passages, and stairwells should be kept unblocked, not locked, and no items should be stacked.

5. Inspection of automatic fire alarm system

1. Check the fault alarm function. Remove a detector and the control device can correctly display the fault alarm signal;

2. Check the fire alarm function. Choose any detector to blow smoke, and the control device can correctly display the fire alarm signal;

3. Check the fire alarm priority function. Remove one detector and blow smoke to the other detector at the same time, and the control device can give priority to the fire alarm signal;

4. Check the fire telephone call. Use fire telephones in the fire control room, pump room, generator room, etc., and the fire control room and relevant places can communicate with each other normally.

6. Inspection of wet sprinkler system

1. The alarm valve assembly is complete, the valves before and after the alarm valve, and the valve leading to the delay device are in the open state;

2. Test the end of the sprinkler system. The linkage control equipment of the fire control room is set in the automatic position, any floor is selected, the end water test is carried out, the water flow indicator action, the control equipment can correctly display the water flow alarm signal, the pressure switch action, the hydraulic alarm bell sends out the alarm, the sprinkler pump starts, and the control equipment can correctly display the pressure switch action and the pump start signal.

7. Inspection of fire hydrants and water pump adapters

1. The water gun, hose and other accessories in the indoor fire hydrant box are complete, and the hose and interface are firmly tied;

2. Check the system function. Choose any indoor fire hydrant, connect the hose and water gun, and the water gun is normal; set the fire control room linkage control equipment in the automatic position, press the start pump button in the fire hydrant box, the fire hydrant pump starts, the control equipment can correctly display the start pump signal, and the water gun is normal;

3. The outdoor fire hydrant is not buried, occupied, or blocked, the logo is obvious, there are special opening tools, the valve opening is flexible and convenient, and the water outlet is normal;

4. The pump adapter is not buried, occupied, or blocked, and is clearly marked, and the type and scope of the water supply system are indicated.

8. Inspection of fire pump room and water supply pipeline water storage facilities

1. The switch on the power distribution cabinet to control the fire hydrant pump, sprinkler pump and pressure stabilizing (boosting) pump is set in the automatic (on) position;

2. The valves of the inlet and outlet pipes of the fire hydrant pump and the sprinkler pump, the valves on the outlet pipe of the high-level fire water tank, and the valves on the pipelines of the automatic sprinkler system and the fire hydrant system are kept normally open;

3. The water volume of high-level fire water storage facilities such as fire water tanks, fire water pools, and pneumatic water tanks reaches the specified water level;

4. There are anti-freezing measures for high-level fire water tanks and indoor and outdoor fire pipes in cold areas in the north.

9. Inspection of smoke prevention and exhaust system

1. Check the pressurized air supply system. The pressurized air supply system is automatically and manually started, the relevant air supply outlet is opened, the blower is started, the air supply is normal, and the feedback signal is correct.

2. Check the smoke exhaust system. The smoke exhaust system is automatically and manually started, the relevant smoke exhaust port is opened, the smoke exhaust fan is started, the exhaust is normal, and the feedback signal is correct.

10. Fire extinguisher inspection

1. The fire extinguisher configuration type is correct, and the place where there is solid combustible materials is equipped with a fire extinguisher that can extinguish Class A fire;

2. The pressure of the pressure storage fire extinguisher meets the requirements, and the pressure gauge pointer is in the green zone;

3. The fire extinguisher is set up in an obvious and easily accessible location, which does not affect the safe evacuation;

4. The fire extinguisher has a record of regular maintenance and inspection.

11. Interior decoration inspection

1. The evacuation stairwell and its front room and the foyer of the safety exit are decorated with non-combustible materials for its ceiling, walls and floors;

2. The ceiling, wall and floor of the room and corridor shall be decorated with decoration materials that meet the requirements of the specification;

3. Reflective mirrors, glass and other decoration materials for safe evacuation without misleading personnel on both sides of the evacuation aisle and near the safety exit.

12. Inspection of exterior wall and roof insulation materials and decoration

1. Understand and master the structure and material use of building exterior wall and roof insulation system;

2. Understand the fire separation or sealing between the floor slab and the external thermal insulation system of the building using flammable and combustible insulation materials on the exterior walls and roofs, as well as the combustion performance of the outermost protective layer materials of the exterior walls and roofs;

3. Buildings that use flammable and combustible thermal insulation and waterproof materials on external walls and roofs have strict fire management systems and strict fire prevention measures.

13. Other examinations

1. The fire main, standby power supply and automatic switching are normal. Switch the main and standby power supplies, check their power supply functions, and the equipment is running normally;

2. The setting and use of electrical equipment, gas appliances, switches, sockets, lighting fixtures, etc., as well as the materials and laying of electrical lines and gas pipelines meet the requirements;

3. Indoor combustible gas and combustible liquid pipelines are made of metal pipes, and emergency shut-off valves are provided;

4. The fire spacing meets the requirements;

5. The fire lane meets the requirements.

If you liked this article, remember to send it to a good friend!

Share wisdom and good luck!

"Disclaimer: This article comes from the Internet and is not an original article on the hotel engineering exchange platform. The reprinted content is only for learning and exchange, the stated views do not represent the position of the hotel engineering exchange platform, the copyright belongs to the original creator, if there is any infringement, please contact us to delete, thank you'