The boiler room and transformer room of the first-level fire engineer technical practice examination center are set up, and the second-level fire engineer is set

The first-level fire engineer technical practice examination center boiler room transformer room is set up, and the second-level fire protection engineer

4. When the boiler room is set up in the oil storage room, its total storage capacity should not be greater than 1m³, and the oil storage room should be separated from the boiler by a fireproof partition wall with a fire resistance limit of not less than 3.00h, and when it is really necessary to open the door on the fireproof partition wall, a Class A fireproof door should be set up.

5. Between the transformer rooms, between the transformer room and the distribution room, a fireproof partition wall with a fire resistance limit of not less than 2.00h should be set.

6. Oil-immersed transformer, multi-oil switch room, high-voltage capacitor room, should be set up to prevent oil dispersion facilities. Accident oil storage facilities that can store the entire amount of oil in the transformer should be set up under the oil-immersed transformer.

7. The capacity of the boiler shall comply with the relevant provisions of the "Boiler Room Design Code" (GB 50041). The total capacity of the oil-immersed transformer should not be greater than 1260kV•A, and the capacity of a single transformer should not be greater than 630kV•A.

8. Fire alarm devices should be set up.

9. Fire extinguishing facilities that are compatible with the capacity of boilers, oil-immersed transformers and the scale of buildings should be set up.

10. The gas boiler room should be equipped with explosion pressure relief facilities, and the gas and oil boiler rooms should be equipped with independent ventilation systems, and should comply with the relevant provisions of the "Code for Fire Protection of Building Design" (GB50016).