Specification | Installation specifications for fire shutter doors

author:Zhang Bobo
Specification | Installation specifications for fire shutter doors
Specification | Installation specifications for fire shutter doors

Last week, I introduced the specifications of fire shutters, and this issue continues to introduce you to the installation and acceptance specifications of fire shutter doors, and follow the editor to look down ~

Installation specifications for fire shutter doors

1. The upper part of the opening of the roller shutter door shall not be equipped with ventilation pipes, water pipes, etc.;

2. The power supply line (three-phase five-wire and fire central control signal line) is laid by the user to the side of the electrical control box next to the rolling door machine;

3. AFTER THE ROLLER SHUTTER DOOR IS INSTALLED, INSTALL THE CEILING, AND THE EDGE OF THE CEILING SHOULD BE 50MM AWAY FROM THE CURTAIN PLATE TO AVOID FRICTION;

4. When debugging and using, it is strictly forbidden to stand at the bottom. Electrical facilities shall not be dismantled without authorization;

5. According to the fire management regulations, the fire shutter door is a special fire protection facility, which shall not be changed for other purposes, and no items shall be stacked directly below the shutter;

6. After installation and commissioning, start once a quarter to check the electrical and mechanical properties, and pay attention to the safety of operation during inspection.

Precautions for installation of fire curtain roller doors

The installation of fire shutter doors is quite important, and the following points need to be paid special attention to when installing.

1. Power supply for fire shutter door

The power supply of the fire shutter door shall be the fire power supply, and the cross-sectional area of the power supply and control wire, insulation resistance, line laying and protection pipe material shall meet the requirements of the specification. The setting value of overcurrent protection of the power supply device of the fire shutter door shall meet the design requirements.

2. Fire shutter door controller

The fire shutter door controller is installed on the fire shutter door to control the fire shutter door to carry out actions such as up, down and stop. It is also necessary to set up manual buttons on both sides (except for the side where personnel cannot operate) to control the lifting, lowering and stopping of the electric fire shutter door, and the function of the fire shutter door should be improved after it is lowered and closed when the fire shutter door is closed, and the fire shutter door should be able to automatically restore the original closed state after being lifted in place.

3. Alarm system of fire shutter door:

The fire shutter door should be equipped with an automatic alarm control system, the electric fire shutter door should be equipped with an automatic closing control device, the fire shutter door on the evacuation channel should be controlled by the detector to descend in two steps or descend to 1.5m~1.8m and then delay the function of descending to the end; for the roller shutter that only plays the role of fire separation, it should be lowered to the end in one step. The arm strength of the manual quick release device of the fire shutter door should not be greater than 50N; the fire control room should have the emergency operation device that forces the electric fire shutter door to descend and display its status; the opening and closing device of the fire shutter door on the evacuation channel should be able to manually and mechanically lift the fire shutter door that has been lowered and closed after the fire power is cut off, and the fire shutter door can rely on its own weight to restore the original closed state. The manual fire shutter door is manually lowered and the traction force is not more than 150N.

After the installation of the fire shutter door, it is necessary to check the above equipment and precautions, and connect the signal line of the fire protection central control to the fire shutter door controller to fully realize the function of the fire protection linkage of the entire fire shutter door.

Acceptance specifications for fire shutter doors

1. The technical requirements that the fire shutter door should meet

1) Average lifting speed: 3m/min.

2) Fire resistance time: 240 minutes.

3) Smoke leakage: 0.18m³/min.

4) Electric up and down, automatic locking, manual opening.

5) After receiving the smoke temperature sensing signal, the roller shutter will automatically make a forced landing.

6) After receiving the signal of the fire control center, it can be forced to land to the bottom or stop at any position.

2. The thickness of the main raw materials shall meet the following requirements:

Specification | Installation specifications for fire shutter doors

3. Appearance requirements

1) The surface of the curtain plate, guide rail, lintel, reel and other parts is not allowed to have cracks, pressure pits and obvious concave and convex, hammer marks, burrs, cavities and other defects.

2) The relative movement must be cleaned in the cutting, bending, punching and other processing places.

3) The assembly and splicing of components or parts are not allowed to be misplaced.

4) The welding place should be firm, the appearance should be smooth, and no slag inclusion, missing welding and other phenomena are allowed.

5) The leakage surface of the parts must be treated with anti-rust, and the coating and plating should be uniform, and there should be no spot peeling.

6) All fasteners must be tightened and no loosening is allowed.

4. The average noise of the opening and closing of the roller shutter and the operation should meet the following requirements:

Specification | Installation specifications for fire shutter doors

5. Main quality requirements

(1) Curtain plate

1.1 The adjacent interlocking curtain plate rotates flexibly after series connection, and the swing ± 900 is not allowed to fall off, and the overlapping curtain with smoke-proof performance is connected in series, and the swing ± 900 is not allowed to fall off.

1.2 The assembly of the baffle plate or anti-channeling mechanism at both ends of the curtain plate should be firm, and the channeling momentum of the curtain shall not be greater than 2mm after being assembled into a roller blind.

1.3 The curtain should be straight, the straightness of the curtain shall not be greater than 1.5mm per meter, and the straightness of the full length shall not exceed 0.12%.

1.4 After the curtain is assembled into a roller shutter, no holes and gaps are allowed.

1.5 The curtain plate with smoke-proof performance should be contacted by the contact surface after the internal and external nose hooks are connected into an arc surface, and the radian angle must be in contact within the range of 300.

1.6 After the curtain is assembled into a roller shutter, it is not allowed to tilt during operation, and it should be lifted in parallel, and the uneven length of the roller shutter is not greater than 1/300 of the height of the hole.

(2) Guide rails

2.1 The depth of the curtain plate embedded in the guide rail shall meet the following requirements:

Specification | Installation specifications for fire shutter doors

2.2 The guide rail with smoke-proof performance must have a smoke-proof device, the material used should be non-combustible materials, the smoke insulation device and the roller shutter table should be evenly and tightly fitted, and the fitting surface should not be less than 80%. 2.2 The top of the guide rail should be rounded, and its length should exceed the hole by at least 75mm.

2.3 The slideway of the guide rail should be smooth and straight, the straightness shall not be greater than 1.5mm per meter, the straightness of the full length shall not be greater than 0.12%, and no twisting, concave and convex, burrs, etc. are allowed.

2.4 The on-site installation of the guide rail should be firm, and the verticality should not be greater than 5mm per meter after installation, and the verticality of the full length should not be greater than 20mm.

2.5 The roller shutter should run smoothly and smoothly in the guide rail, and no collision or impact is allowed.

(3) Lintel

3.1 The structure of the lintel must effectively prevent the spread of fire.

3.2 The lintel with smoke-proof performance must be equipped with a smoke-proof device to effectively prevent the smoke from overflowing, and all materials of the smoke-proof device should be non-combustible materials.

3.3 The smoke prevention device of the lintel is in uniform contact with the sealing surface of the lintel and the surface of the roller shutter, the contact surface should not be less than 80% of the width of the door opening, and the gap between the non-contact surface should not be greater than 2mm.

3.4 The on-site installation of the lintel should be firm, and the spacing of the embedded steel parts shall not be greater than 600mm.

(4) Seat board

4.1 The contact between the seat board and the ground should be uniform and parallel.

4.2 The seat plate should be composed of angle steel, the size of the angle steel should be determined according to the width of the hole, rivet connection or bolt connection, the spacing is not more than 300mm.

(5) Transmission

5.1 The installation of the rolling door machine must leave room for maintenance, and the installation should be firm and not leaking.

5.2 The bearing is installed firmly, the bearing is not abnormal, and the oil is sufficient.

5.3 The sprocket center of each rotating shaft should be coaxial and undamaged.

5.4 There are two kinds of rolling door machine: electric and manual, and the fire shutter must be equipped with a fire shutter door machine or an ordinary rolling door machine with a fire insulation device, and the fire resistance test certificate should be obtained.

(6) Electrical installation

6.1 The operation of the electrical button is flexible, and the action of centralized control and linkage control is flexible and accurate.

6.2 The safety device of automatic control shall be installed in the exposed part within 2m range near the roller shutter and the part that can be monitored at any time. There are control buttons inside and outside the fire shutter door.

6.3 The automatically controlled power supply, backup power supply or battery should be able to maintain normal working condition, and the electrical wiring used should not be exposed, and should be buried in the wall or have a threading pipe.

6.4 Installation requirements for steel fire shutters and walls:

The steel fire shutter is installed on the wall of the building, and should be connected by welded or embedded bolts, and the original building can be assembled with expansion bolts on the concrete wall or concrete column, and the installation strength should be ensured to meet the design requirements.

If you liked this article, remember to send it to a good friend!

Share wisdom and good luck!

"Disclaimer: This article comes from the Internet and is not an original article on the hotel engineering exchange platform. The reprinted content is only for learning and exchange, the stated views do not represent the position of the hotel engineering exchange platform, the copyright belongs to the original creator, if there is any infringement, please contact us to delete, thank you'