recently

Sanya City has taken multiple measures to carry out investigation and rectification

Make every effort to eliminate the hidden danger of fire

Concentrated exposure of the eighth batch of 11 fire hazard units

Warning social units to strengthen fire safety management

01 Poly Property Co., Ltd. Sanya Branch

(Poly Haitang Community Phase II)

Unit address: No. 33, Jianglin Road, Haitang District, Sanya City

Hidden Problems:

1. There is a fault in part of the evacuation indication sign on the basement floor;

2. The wet alarm valve discharge test, the pressure switch of the alarm valve group has no action, and the sprinkler fire pump has not started;

3. The fire linkage controller cannot cut off the non-fire power supply in the relevant area;

4. The fire shutter on the basement floor cannot be lowered in tandem;

5. Some green plants block the indoor fire hydrant.

02 Sanya Haitang District School Care Worry-free Student Care Station

Unit address: Xinmin Road, Haitang District, Sanya City

Hidden Problems:

1. The kitchen is not separated from other parts by fireproof;

2. The external window is illegally set up with anti-theft nets that affect fire fighting, rescue and escape;

3. The kitchen is not equipped with a fire blanket;

4. The number of fire extinguishers is insufficient;

5. There are no evacuation and self-rescue equipment such as escape ropes, filtering self-rescue breathing apparatus and emergency flashlights;

6. The distance between the long sides of the two single beds is insufficient;

7. The per capita usable area of the dormitory is insufficient;

8. The number of safety exits in the premises is insufficient;

9. No evacuation schematic diagram is set;

10. No independent smoke fire detection alarm is set;

11. Evacuation lighting fixtures and light evacuation indication signs are not set up;

12. Failure to organize all staff to carry out initial fire fighting and evacuation drills every quarter as required;

13. Failure to organize fire safety training and emergency evacuation drills for students every six months as required.

03 Sanya Yuanqi Trading Co., Ltd

Unit address: B1, Building 7, Phase 14, Tongxin Home, No. 535, Yuya Road, Jiyang District, Sanya City

Hidden Problems:

1. The smoke exhaust port of the mechanical smoke exhaust system is not set in the smoke storage bin;

2. The height of the manual actuator set by the mechanical smoke exhaust system exceeds 1.5 meters;

3. The fire separation of the smoke exhaust fan room is not in place;

4. The width of the supermarket safety exit does not meet the requirements of the specification (the design width is 11.95 meters, the actual width is 9 meters, and the two safety exits are evacuated from the warehouse area, and the fire separation is not counted);

5. There is no sprinkler protection under the air duct of the 1.2-meter-wide mechanical smoke exhaust system;

6. There are two kinds of fire hydrants in the indoor fire hydrant: the pressure of the ordinary type fire hydrant is more than 0.7Mpa, and the pressure reduction type fire hydrant is 0.65Mpa;

7. A number of indoor fire hydrants in the warehouse are not kept intact and effective (the fire hydrant mouth is lost, the hose is aging, rusty and leaking);

8. The hose reel in the indoor fire hydrant box is not kept intact and effective (the pipeline is folded and leaking);

9. The automatic fire alarm system fails to realize the linkage function;

10. The indoor height of the supermarket is greater than 3.5 meters, and medium and large evacuation signs are not used;

11. There are no evacuation indication signs in the evacuation passages on the southeast and southwest sides of fire prevention zone 1 and fire prevention zone 2 in the supermarket;

12. The fire control room is not effectively separated by fire protection;

13. The fire control room fails to meet the requirements of two people holding a certificate for 24 hours;

14. The cable shaft in the supermarket is not in place to pass vertically through the floor slab;

15. The direction of the evacuation indication signs in many places in the safety exit and supermarket is wrong;

16. The fire shutter separation at the fire partition is not in place;

17. A fire shutter should be set at the location of the Class A fire door at the separation of the fire partition;

18. THE GAP BETWEEN THE DOOR LEAF OF THE NORTHEAST AND NORTHWEST SIDE SAFETY EXIT FIRE DOOR AND THE GROUND IS GREATER THAN 9MM;

19. The office in the warehouse is not equipped with fire separation and independent evacuation stairs;

20. There are no automatic sprinkler facilities in the office and the small warehouse of the office;

21. There are no smoke detectors in the office and the small warehouse of the office;

22. The transmission line of the automatic fire alarm system is not protected by metal and other pipe fittings;

23. The emergency broadcasting system is not kept intact and effective;

24. Two smoke exhaust methods are set up in the same smoke-proof zone in the supermarket: mechanical smoke exhaust and natural smoke exhaust.

04 Guangyou Mingpinhui Tea House, Jiyang District, Sanya

Unit address: No. 110, Yuya Road, Jiyang District, Sanya City (formerly Yuhai Building)

Hidden Problems:

1. The number of safety exits in the place is insufficient;

2. The wall decoration and decoration materials in the business area of the place fail to provide fire resistance certificates;

3. There are no smoke exhaust facilities in the evacuation corridor of the place with a length of more than 20 meters;

4. The illumination of the evacuation corridor and the emergency lighting in the box in the place is insufficient;

5. There is no fire separation between the kitchen and the business area.

05 Sanya Yalong Bay Golf Club Co., Ltd

Unit address: Yalong Bay National Tourism Resort, Jiyang District, Sanya City

Hidden Problems:

1. The safety exit sign on the west side of the fourth floor on the ground is not kept intact and effective, and the sprinkler head of the automatic sprinkler system in the guest kitchen is not kept intact and effective;

2. No fire drill was carried out, and there were less than 2 certified personnel in the fire control room.

06 Beijing China Railway Hui Life Technology Service Co., Ltd

(China Railway Youlanhu Community)

Unit address: No. 472, middle section of Yingbin Road, Jiyang District, Sanya City

Hidden Problems:

1. Most of the evacuation signs and a small number of emergency lighting on floors 1 to 25 above ground in buildings 1 to 3 and 5 to 8 are not kept intact and effective;

2. There are 120 failure points in the controller of the automatic fire alarm system that have not been handled;

3. Some of the evacuation passages and evacuation stairwells on floors 1 to 25 above ground of buildings 1 to 3 and 5 to 8 occupy the evacuation passages;

4. Fire prevention inspections, training drills and duty records do not meet the requirements.

07 Sanya Hongjian Commercial Investment Co., Ltd

Sanya Phoenix Branch

Unit address: Yangxin Neighborhood Committee, Fenghuang Town, Tianya District, Sanya City

Hidden Problems:

1. There are faults in the evacuation indication signs on some floors, and the pressure of the fire extinguisher is insufficient;

2. The daily fire inspection record does not meet the requirements.

08 Sanya Hexi Sunflower Kindergarten

Unit address: Turn right on the first floor of Meiduo Hotel at the intersection of Heping Street and Shengli Road, Tianya District, Sanya City

Hidden Problems:

1. Failure of evacuation indication signs in some areas;

2. There are no employee training records, drill records, and fire protection files.

09 Sanya Grain Reserve Management Company

Unit address: Youyi Road, Tianya District, Sanya City

Hidden Problems:

1. Some electrical lines in the reservoir area are not laid through flame retardant pipes as required;

2. The fire separation between some reservoir areas does not meet the requirements.

10 Sanya Hongtang Blue Ocean Hotel Management Co., Ltd

Unit address: No. 166, Maling Street, Tianya District, Sanya City

Hidden Problems:

1. The electric safety bolt of the gas cylinder of the gas fire extinguishing system is not pulled, the voltage stabilization system of the outdoor fire hydrant cannot be started, the power backup working status of the automatic fire alarm system is tested, and the circuit of the fire emergency broadcast is disconnected and faulty.

2. The height of the pressure relief port in the protection area of some heptafluoropropane fire extinguishing systems is less than 2/3 of the net height of the protection area;

3. The opening of the fireproof partition wall separated by the blower room and the basement walkway is not blocked with materials that meet the requirements of the fire resistance limit;

4. The distance between the electrical circuit panel and the curtain behind the large electronic display screen on the stage is less than 500mm;

5. The warehouse behind the stage did not set up an automatic fire extinguishing system as required.

11 Sanya Yacheng Fanghao Travel Rental

Unit address: No. 67, Yazhou Road, Yazhou District, Sanya City

Hidden Problems:

1. The hose of the fire extinguisher on the floor is damaged, and the filtering self-rescue pager fails;

2. The independent smoke detector on the floor is faulty and the setting does not meet the requirements;

3. Floor emergency lighting failure;

4. There is no emergency escape window on the anti-theft network in the guest room;

5. A large number of combustibles are piled up in the stairwell on the first floor.

In response to the problems found in the inspection, Sanya Fire tracks and supervises the rectification and improvement of hidden dangers in relevant units, regularly carries out return visits and inspections, eliminates fire hazards in a timely manner, and ensures that the fire safety situation in the city continues to be stable.

11 units!
11 units!

I've asked for you, AI doesn't understand Sanya!

11 units!

Outstanding achievements! National Commendation!

11 units!

Another batch!

11 units!

Source: Sanya Fire and Rescue Detachment