CA9010 bus isolation module wiring diagram:
Bus isolation module base terminal wiring instructions:
(1) 6 (IN-), 5 (IN+): The input of the loop bus, connected to the two return routes from the fire alarm control
(2) 4 (OUT-), 3 (OUT+): The output of the loop bus, leading to the signal two-bus terminal of the loop front-end device
CA9001 photoelectric smoke fire detector wiring diagram:
Wiring instructions:
1 (SLC+), 3 (SLC-) terminal: a loop bus connected from the loop terminal of the fire alarm controller, no polarity
CA9006 manual fire alarm button wiring diagram:
Wiring instructions:
(1) 5 (SLC-), 6 (CLC+) terminals: connected to the loop bus attracted from the fire alarm controller, no polarity
(2) 3 (TEL1), 4 (TEL2) terminal: the telephone line attracted by the fire switchboard, no polarity
CA9006X type hydrant button wiring diagram:
Wiring instructions:
(1) 1 (COM), 2 (ON) terminal: passive contact output, used to start the fire pump (Note: used according to fire regulations)
(2) 5 (SLC-), 6 (CLC+) terminals: connected to the loop bus attracted from the fire alarm controller, no polarity
CA9007 input module wiring diagram:
Wiring instructions:
(1) 3 (A1), 4 (A2) terminal: connect the feedback line of the starting device (passive normally open of the controlled device)
(2) 5 (SLC-), 6 (SLC+) terminals: connected to the loop bus attracted from the fire alarm controller, no polarity
CA9008 type input and output module wiring diagram
Active 24V normally open output:
Active 24V normally open output base terminal wiring instructions:
(1) 1 (24V+), 2 (24V-) terminal: connect to the 24V power line
(2) 3 (A1), 4 (A2) terminal: connect the feedback line of the starting device (passive normally open of the controlled device)
(3) 5 (SLC-), 6 (SLC+) terminals: connected to the loop bus attracted from the fire alarm controller, no polarity
(4) 10 (COM), 11 (V-) terminals: terminal short tangent
(5) 9 (NO), 12 (V+): output active 24V normally open output
Passive normally open output:
Passive normally open output base terminal wiring instructions:
(1) 1 (24V+), 2 (24V-) terminal: connect to the 24V power line
(2) 3 (A1), 4 (A2) terminal: connect the feedback line of the starting device (passive normally open of the controlled device)
(3) 5 (SLC-), 6 (SLC+) terminals: connected to the loop bus attracted from the fire alarm controller, no polarity
(4) 9 (NO), 10 (COM) terminal: passive normally open control output
Fire sound and light siren wiring diagram:
Base terminal wiring instructions:
(1) S+, S- terminal: connected to the loop bus attracted from the fire alarm controller, no polarity
(2) +, - terminal: connected to 24V power line, polarity
CA6107 bus broadcast module wiring diagram:
Base terminal wiring instructions:
(1) 1 (24V+), 2 (24V-) terminal: connect to the 24V power line
(2) 5 (IN+), 6 (IN-) terminals: connected to the loop bus attracted from the fire alarm controller, no polarity
(3) 7 (IN2+), 8 (IN2-) terminals: normal background broadcast line access
(4) 9 (OUT+), 10 (OUT-) terminal: broadcast outlet connected to live sound
(5) 11 (IN1+), 12 (IN1-) terminal: connect to the fire amplifier
CA2101 fire display panel wiring diagram:
Base terminal wiring instructions:
(1) BUS1, BUS2 terminal: connected to the loop bus attracted from the fire alarm controller, no polarity
(2) 24V+, GND terminal: connected to 24V power line, polarity