一、連接配接圖如下

二、發送指令如下
1、煙霧:
02 04 00 02 00 01 90 39
2、溫濕度:
01 03 00 00 00 03 05 cb
3、UPS(深圳山特)
Q6
(229.6 000.0 000.0 50.0 218.8 ---.- ---.- 50.0 001 --- --- 215.2 ---.- 21.8 65535 100 30 00000000 00000000 00
[0] = 299.6 UPS輸入R相電壓
[1] = 000.0 UPS輸入S相電壓
[2] = 000.0 UPS輸入T相電壓
[3] = 50.0 UPS輸入頻率
[4] = 218.8 UPS輸出R相電壓
[5] = ---.- UPS輸出S相電壓
[6] = ---.- UPS輸出T相電壓
[7] = 50.0 UPS輸出頻率
[8] = 001 UPS輸出R相電流
[9] = --- UPS輸出S相電流
[10] = --- UPS輸出T相電流
[11] = 215.2 UPS電池正極電壓
[12] = --- UPS電池負極電壓
[13] = 21.8 UPS溫度
[14] = 65535 UPS電池剩餘備用時間估計
[15] = 100 UPS電池容量百分比
[16-0] = 3 UPS系統模式
[16-1] = 0 UPS電池測試狀态
[17] = 00000000 UPS故障代碼
[18] = 00000000 UPS警告
[19] = 00 未知
4、聲光報警器
開啟指令:
01 05 00 00 ff 00 8C 3A
關閉指令:
01 05 00 00 00 00 CD CA